Skip to content
Omron LY2 AC110/120 general purpose relay 2 changeover contacts 110/120 V AC

Omron LY2 AC110/120 general purpose relay 2 changeover contacts 110/120 V AC

Schirmer item number
2278
Manufacturer
OMRON

Available on request

Price on request

What happens next

We will get back to you as soon as possible with all the details.

No obligation Fast response

Secure payment methods

VisaMastercardInvoice (business customers)Prepayment

Insured shipping

All items are shipped insured, including DHL tracking. Express shipping is available on request.

Questions about this product?

Please compare the model and version with your part. Unsure about compatibility or what is included? Ask us about this item.

Product details & specifications

The LY2 AC110/120 is an electromechanical general purpose relay with two changeover contacts and an AC coil for 110/120 V. The contacts are made of a silver alloy, and an integrated arc chamber separates the switching arc.

General

ManufacturerOmron
Type / modelLY2 AC110/120
Article number2278
Order numberLY2 AC110/120
SeriesLY

Technical data

Contact configuration2 changeover contacts (DPDT)
Rated coil voltage110/120 V AC
Rated coil current 50 Hz9.9/10.8 mA
Rated coil current 60 Hz8.4/9.2 mA
Coil resistance4,430 Ω
Must-operate voltagemax. 80 % of rated voltage
Must-release voltagemin. 30 % of rated voltage
Maximum coil voltage110 % of rated voltage
Coil power consumptionapprox. 0.9 to 1.1 VA (60 Hz)
Contact materialsilver alloy
Rated load, resistive10 A at 110 V AC, 10 A at 24 V DC
Rated load, inductive (cos φ 0.4, L/R 7 ms)7.5 A at 110 V AC, 5 A at 24 V DC
Continuous current10 A
Maximum switching voltage250 V AC, 125 V DC
Maximum switching current10 A
Contact resistancemax. 50 mΩ
Operate timemax. 25 ms
Release timemax. 25 ms
Insulation resistancemin. 100 MΩ (500 V DC)
Test voltage coil/contact and contacts of different polarity2,000 V AC, 50/60 Hz, 1 min
Test voltage contacts of same polarity1,000 V AC, 50/60 Hz, 1 min
Mechanical endurancemin. 50,000,000 operations (AC)
Electrical endurancemin. 500,000 operations at rated load
Shock resistance1,000 m/s² (destruction), 200 m/s² (malfunction)
Ambient temperature-25 to 55 °C
Humidity5 to 85 %
Weight40 g
Arc chamberyes

Frequently asked questions